YASKAWA
TOEPYAIGA5002A GA500 Programming
195
Note:
•
You cannot select
parameter U5-xx
.
•
This parameter is disabled when set to
000
.
■
b5-56: PID Feedback Monitor Gain
No.
(Hex.)
Name
Description
Default
(Range)
b5-56
(0BE2)
PID Feedback Monitor Gain
Sets the gain for the monitor set in
b5-55 [PID Feedback Monitor Selection]
.
1.00
(0.00 - 10.00)
■
b5-57: PID Feedback Monitor Bias
No.
(Hex.)
Name
Description
Default
(Range)
b5-57
(11DD)
PID Feedback Monitor Bias
Sets the bias for the monitor specified in
b5-55 [PID Feedback Monitor Selection]
.
0.00
(-10.00 - +10.00)
■
b5-58 to b5-60: PID Setpoints 2 to 4
No.
(Hex.)
Name
Description
Default
(Range)
b5-58 to b5-60:
(1182 - 1184)
RUN
PID Setpoints 2 to 4
Sets the PID setpoint when
H1-xx = 3E or 3F [MFDI Function Selection = PID Setpoint Selection 1/
2]
. This value is a percentage of the maximum output frequency.
0.00%
(0.00 - 100.00%)
shows how the different MFDI
H1-xx
values (
3E and 3F
) have an effect on the PID setpoint value.
Table 2.29 Switching of MFDI and PID Setpoint Value
H1-xx = 3E
H1-xx = 3F
PID Setpoint Value
OFF
OFF
No switch
ON
OFF
b5-58 [PID Setpoint2]
OFF
ON
b5-59 [PID Setpoint3]
ON
ON
b5-60 [PID Setpoint4]
■
b5-61: PID Trim Mode Lower Limit Sel
No.
(Hex.)
Name
Description
Default
(Range)
b5-61
(119A)
PID Trim Mode Lower Limit
Sel
Sets the function that adjusts the PID output in relation to the frequency reference.
0
(0, 1)
0 : Disabled
Does not adjust the PID output with the frequency reference.
1 : Enabled
Adjusts the PID output in relation to the frequency reference. The setting value of
b5-62 [PID Trim Mode Lower
Limit Value]
sets the lower limit of the post-adjustment value. The maximum output frequency sets the upper limit.
Note:
•
Set
b5-01 = 3, 4, 7, or 8
to enable this parameter.
•
When
b5-61 = 1
, you can use this formula to adjust PID output proportional to the frequency reference:
U5-03 [PID Output]
,
Fref [Frequency Reference]
, and
Fmax [Maximum Output Frequency]
*1
Lower limit =
b5-62
, Upper limit = Maximum output frequency
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...