YASKAWA
TOEPYAIGA5002A GA500 Programming
101
No.
(Hex.)
Name
Description
MFAO Signal Level
U4-19
(07DB)
Modbus FreqRef (dec)
Shows the frequency reference sent to the drive from the MEMOBUS/Modbus communications as a
decimal.
Unit: 0.01%
10 V: Maximum frequency
(0 V to +10 V)
U4-20
(07DC)
Option Freq Ref(dec)
Shows the frequency reference sent to the drive from the communication option as a decimal.
10 V: Maximum frequency
(0 V to +10 V)
U4-21
(07DD)
Run Command Source
Shows the selected Run command source.
The keypad shows the Run command source as
“
XY-nn
”
as specified by these rules:
X:
External Reference 1/2 Selection [H1-xx = 2]
selection status
•
1:
b1-02 [Run Command Selection 1]
•
2:
b1-16 [Run Command Selection 2]
Y: Run command source
•
0: Keypad
•
1: Control circuit terminal
•
3: MEMOBUS/Modbus communications
•
4: Communication option card
•
7: DriveWorksEZ
nn: Run command limit status data
•
00: No limit status.
•
01: The Run command was left ON when the drive stopped in the Programming Mode.
•
02: The Run command was left ON when switching from LOCAL Mode to REMOTE Mode.
•
03: The Run command is in standby after the drive was energized until the soft charge bypass
contactor turns ON.
Note:
The drive will detect
Uv1 [DC Bus Undervoltage]
or
Uv [Undervoltage]
if the soft charge
bypass contactor does not turn ON after 10 s.
•
04: Restart after run stop is prohibited.
•
05: Fast stop has been executed using the MFDI terminal. Or, the motor has ramped to stop by
pressing the STOP key on the keypad.
•
06:
b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command]
is set.
•
07: During baseblock while coast to stop with timer.
•
08: Frequency reference is below
E1-09 [Minimum Output Frequency]
during baseblock.
•
09: Waiting for the Enter command from PLC.
No signal output The keypad
shows the Run command
source as "XY-nn" as
specified by these rules:
available
U4-22
(07DE)
Modbus CmdData (hex)
Shows the operation signal (register 0001H) sent to the drive from MEMOBUS/Modbus
communications as a 4-digit hexadecimal number (zero suppress).
The keypad shows the operation signal as specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset Procedure
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Not used (normal value of 0).
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
No signal output available
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...