TOEPYAIGA5002A GA500 Programming
27
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C3-24
(0243)
Motor 2 Slip Comp
during Regen
Sets the slip compensation during regenerative operation function for motor 2.
0 : Disabled
1 : Enabled Above 6Hz
2 : Enabled Above C3-15
0
(0 - 2)
C3-29
(1B5D)
Expert
Slip Compensation Gain
@ Low Spd
Sets the gain for the slip compensation function in the low speed range. Usually it is not
necessary to change this setting.
0.0
(0.0 - 2.5)
◆
C4: Torque Compensation
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C4-01
(0215)
RUN
Torque Compensation
Gain
Sets the gain for the torque compensation function. Use this parameter value for motor 1
when operating multiple motors.
Note:
When
A1-02 = 8 [Control Method Selection = EZOLV]
, you cannot change this
parameter during drive run.
Determined by A1-02
(0.00 - 2.50)
C4-02
(0216)
RUN
Torque Compensation
Delay Time
Sets the torque compensation delay time. Usually it is not necessary to change this setting.
Note:
If
A1-02 = 8 [Control Method Selection = EZOLV]
, you cannot change the setting
while the drive is running.
Determined by A1-02
(0 - 60000 ms)
C4-03
(0217)
Torque Compensation @
FWD Start
Set the amount of torque reference for forward start as a percentage of the motor rated
torque.
0.0%
(0.0 - 200.0%)
C4-04
(0218)
Torque Compensation @
REV Start
Sets the amount of torque reference for reverse start as a percentage of the motor rated
torque.
0.0%
(-200.0 - 0.0%)
C4-05
(0219)
Torque Compensation
Time
Sets the starting torque constant to use with
C4-03 and C4-04 [Torque Compensation @
FWD/REV Start]
.
10 ms
(0 - 200 ms)
C4-06
(021A)
Motor 2 Torque Comp
Delay Time
Sets the value if
ov [Overvoltage]
occurs with sudden changes in the load, at the end of
acceleration, or at the start of deceleration.
150 ms
(0 - 10000 ms)
C4-07
(0341)
RUN
Motor 2 Torque
Compensation Gain
Sets the gain for motor 2 torque compensation function when using the Motor Switch
function.
1.00
(0.00 - 2.50)
C4-23
(1583)
RUN
Expert
Current Control Gain
Current control gain. Usually it is not necessary to change this parameter.
1.00
(0.50 - 2.50)
◆
C5: Automatic Speed Regulator (ASR: Automatic Speed Regulator)
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C5-01
(021B)
RUN
ASR Proportional Gain 1
Sets the gain to adjust ASR response.
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
Determined by A1-02
(0.00 - 300.00)
C5-02
(021C)
RUN
ASR Integral Time 1
Sets the ASR integral time.
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
Determined by A1-02
(0.000 - 60.000 s)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...