190
YASKAWA
TOEPYAIGA5002A GA500 Programming
Applies a gain to the PID output and can help when
b5-01 = 3 or 4 [PID Mode Setting = Fref + PID Trim, Fref +
PID Trim (D on feedback)]
.
■
b5-11: PID Output Reverse Selection
No.
(Hex.)
Name
Description
Default
(Range)
b5-11
(01AF)
PID Output Reverse
Selection
Sets the function that enables and disables reverse motor rotation for negative PID control output.
0
(0, 1)
This parameter is disabled when
b5-01 = 3, 4 [PID Mode Setting = Fref + PID Trim, Fref + PID Trim (D on
feedback)]
. There is no limit for PID output (PID output can be positive or negative). Operates the same as setting
“
1:
Enabled: Negative lower limit
”
.
0 : Lower Limit is Zero
When PID output is negative, PID output is limited to 0 and drive output is shut off.
1 : Negative Output Accepted
When the PID output is negative, the motor will rotate in reverse. When
b1-04 = 1 [Reverse Operation Selection =
Reverse Disabled]
, the lower limit is 0.
■
b5-12: Feedback Loss Detection Select
No.
(Hex.)
Name
Description
Default
(Range)
b5-12
(01B0)
Feedback Loss Detection
Select
Sets the drive response to PID feedback loss/excess. Sets drive operation after the drive detects PID
feedback loss/excess.
0
(0 - 5)
0 : Digital Out Only, Always Detect
The MFDO terminal set for
PID Feedback Low
or
PID Feedback High [H2-01 to H2-03 = 3E, 3F]
activates. When
the drive detects feedback loss/excess, the keypad will not show an alarm and the drive will continue operation.
When the feedback signal is less than the level set in
b5-13 [PID Feedback Loss Detection Lvl]
for longer than the
time set in
b5-14 [PID Feedback Loss Detection Time]
, the MFDO terminal set for
PID Feedback Low
activates.
When the feedback signal is more than the level set in
b5-36 [PID High Feedback Detection Lvl]
for longer than the
time set in
b5-37 [PID High Feedback Detection Time]
the MFDO terminal set for
PID Feedback High
activates.
When the feedback value is not in the detection range, the drive resets the MFDO.
1 : Alarm + Digital Out, Always Det
The drive detects
FbL [PID Feedback Loss]
and
FbH [Excessive PID Feedback]
. The MFDO terminal set for
PID
Feedback Low
or
PID Feedback High [H2-01 to H2-03 = 3E, 3F]
activates. The output terminal set for
Alarm [H2-
01 to H2-03 = 10]
activates and the drive continues operation.
When the feedback signal is less than the level set in
b5-13
for longer than the time set in
b5-14
, the MFDO terminal
set for
PID Feedback Low
activates.
When the feedback signal is more than the level set in
b5-36
for longer than the time set in
b5-37
, the MFDO terminal
set for
PID Feedback High
activates.
When the feedback value is not in the detection range, the drive resets the MFDO.
2 : Fault + Digital Out, Always Det
The drive detects
FbL
and
FbH
. MFDO terminal MA-MC turns ON, MB-MC turns OFF, and the motor coasts to
stop.
When the feedback signal is less than the level set in
b5-13
for the time set in
b5-14
, the drive detects
FbL
.
When the feedback signal is more than the level set in
b5-36
for the time set in
b5-37
, the drive detects
FbH
.
3 : Digital Out Only, @ PID Enable
The MFDO terminal set for
PID Feedback Low
or
PID Feedback High
activates. The keypad will not show an alarm.
The drive continues operation.
When the MFDI terminal set to
PID Disable [H1-xx = 19]
activates, the drive disables fault detection.
4 : Alarm + Digital Out, @PID Enable
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...