2.8 H: Terminal Function Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
299
shows an example of how fast stop operates.
Figure 2.66 Fast Stop Time Chart
■
18: Timer Function
Setting Value
Function
Description
18
Timer Function
Sets the command to start the timer function. Use this setting with
Timer Output [H2-xx = 12]
.
Note:
Refer to
“
b4: Timer Function
”
for more information.
■
19: PID Disable
Setting Value
Function
Description
19
PID Disable
Sets the command to disable PID control when
b5-01 = 1 to 8 [PID Mode Setting = Enabled]
.
ON : PID control disabled
OFF : PID control enabled
■
1A: Accel/Decel Time Selection 2
Setting Value
Function
Description
1A
Accel/Decel Time Selection
2
Set this function and
H1-xx = 7[Accel/Decel Time Selection 1]
together. Sets the drive to use
Acceleration/Deceleration Time 3 [C1-
05, C1-06]
or
Acceleration/Deceleration Time 4 [C1-07, C1-08]
.
Note:
Refer to
C1: Accel & Decel Time on page 204
for more information.
■
1B: Programming Lockout
Setting Value
Function
Description
1B
Programming Lockout
Sets the command to prevent parameter changes when the terminal is OFF.
You can continue to view parameter setting values when the terminal is
OFF [Parameters Cannot be Edited]
.
ON : Program Lockout
OFF : Parameter Write Prohibit
■
1E: Reference Sample Hold
Setting Value
Function
Description
1E
Reference Sample Hold
Sets the command to sample the frequency reference at terminal A1 or A2, and hold the frequency reference at that frequency.
When the terminal is active for 100 ms, this function reads a sample of the analog frequency reference and holds that
sample. When you input the sample/hold command again, the function again reads a sample of the analog frequency
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...