35
14.2.3 Colour code - motor line
The overview fields on the touchscreen have colour codes for the motor lines:
Colour
Meaning
Yellow triangle icon
The motor line are to be configured or there is a fault in the actuator
Strikethrough grey
No configuration of the motor line / the motor line doesn’t exists
Black text
The motor line are configured, the actuator has not been closed
Green
The motor line has been configured; the actuator has been closed
MotorLink
®
motor lines will be marked in green, if the actuator / actuators on the motor
line has been closed 100% and the point zero of the actuator has been determined.
Light grey number
The motor line are configured with ‘No actuator are connected’
Blue
?
Configuration is missing or there is a mistake in the configuration
Red
The motor line has been given alarm signal
14.3 Motor group
All motor groups are to be assigned to a smoke zone and multiple motor groups can be assigned to the same smoke zone.
See the example "Example of motor lines / motor groups / smoke zones" in the beginning of this chapter for further details.
When configuration specify the number of the smoke zone that are to control the motor group.
14.3.1 Motor group - configuration
Press ”Motor group” and the overview of the motor groups in the smoke ventilation panel is shown.
Motor group configuration
Motor group overview
Motor groups are to be configured in:
1.
Controlling smoke zones
2.
Comfort open position
3.
Comfort open close time
4.
Use ‘safety‘ from smoke zone
5.
Wind directions where to close during alarm
The appendix contains all the items that can be configured
- see appendix for detailed explanation.
14.3.2 Colour code
– motor group
The overview fields on the touch screen have colour codes for the motor groups:
Colour
Meaning
Yellow triangle icon
One or more of the assigned motor lines has a failure
Black text
The motor group is configured
Green field
All the assigned motor lines are closed
Light grey number
The motor group is configured but no motor lines are assigned
Blue
?
Configuration is missing or there is a mistake in the configuration
Red
The motor group has been given alarm signal
14.4 Break glass unit
A break glass unit shall be assigned to a smoke zone and multiple break glass units can be assigned to the same smoke zone.
See the example "Example of motor lines / motor groups / smoke zones" in the beginning of this chapter for further details.
14.4.1 Break glass unit
– configuration
First the break glass units must be configured according to the topology (if they are connected one by one or in a ring) and then
follow the individual configuration of the break glass units according to smoke zones, comfort motor groups etc.
To be sure it is the right glass break unit that is configured; it is possible to locate the break glass unit in one of two ways:
1. Press the reset button and a blue speech bubble will appear in the selected break glass unit in the overview of the break
glass units.