11
Material
Metal housing for surface mounting
Colour
Grey (RAL 7035)
Size
WSC 310: 300 x 400 x 120mm (HxWxD)
WSC 320: 300 x 400 x 210mm (HxWxD)
Weight
WSC 310: 6kg no batteries, 10.8kg with batteries (2 x WSA 007)
WSC 320: 8.6kg no batteries, 16.6kg with batteries (2 x WSA 012)
Protection class
IP54
Approval / certification
Approved and certified according to EN 12101-10
Delivery
CompactSmoke™ smoke ventilation panel with WSA 501 (10kΩ resistors, 10
pcs.) and 2 oder 10 pcs. end of line module WSA 510
Back-up batteries included.
Note
We reserve the right to make technical changes
6
Mounting
The smoke ventilation panel is fixed to the wall through the Ø8.5mm holes in the
back plane of the housing.
If the panel is fixed in different way, the holes are to be blinded with the 4 blind
grommets, this way the IP class is maintained.
The door is turnable.
When turning the door also move the blind grommets to the new holes.
The smoke ventilation panel is to be located in a safe place, protected from the
effects of fire and smoke.
7
Installation
7.1 Cable routing
For cable routing, we recommend the use of fire protected cables retaining their function E90 or E30.
See also chapter 8 “Cable dimensioning” in this instruction.
However, this has to be agreed with the Engineer or, if necessary, with the local fire protection department.
Do not reduce the cable cross sections specified in the cable lengths table.
All cables of the control (except the mains supply cable) carry 24V DC and have to be routed separate from the mains supply
cable.
Adhere to the pertinent national and local regulations when routing the cables.
7.2 Cables into housing
All connection terminals (except the mains terminals) are of the plug-in type.
Connect the connection cables in accordance with the terminal plan. Ensure that the connections are made correctly.
Incorrect cable clamping, mixing up numbers or colours could lead to malfunctions of the control panel or of the external
components.
Ensure that the electrical cables are always routed according to the valid national and local regulations.
7.3 Connection of safety earth wire and 230V AC
See chapter
10 ‘Description of cards’, section 10 for further description.
7.4 Installation of the break glass unit, ventilation keypad and smoke detector
Ensure that the break glass unit and the ventilation buttons are visible and well accessible. Do not install behind protruding
walls, door panels or hidden by the building structure.
Note
: Installation height of the break glass unit 1.5
– 1.7m above floor.
Install the smoke detectors in accordance with their enclosed instructions.