The CompactSmoke™ is tested with Hekatron THM 425-1.
Technical data (of Hekatron):
Configuration of magnetic clamp
Configuration of magnetic clamp
The configuration of magnetic clamp must be done for each motor
line.
Under the configuration of Motors line select Magnetic clamp.
Each motor line which is configured to a magnetic clamp must be
associated with a motor group.
14.11
Master / Slave connection of smoke zones
The master/slave connection between two panels is done via input X5 or X6 on the master panel
– the input, also used for
connection to a break glass unit
– and input X11 on the slave panel.
A smoke panel can have a master/slave connection to several smoke panels. However, the total max number of connected
slaves AND break glass units on the bus must not exceed 10 units.
The total cable length must not exceed 200m, see examples below for how to connect the panels.
A slave panel can only have one master, whereas a master panel can have several slaves and a panel can both be a slave and
a master to other panels.