14.9 Sequence control
The sequence control functionality is used where the movement of a motor line must depend on an external event or
situation/stage.
To be used where window flabs are overlapping or where the windows cannot open (more than 15%) if the blinds are down a.s.o.
The sequence control can be controlled depending on;
- the position of a different motor line
- the state of a local input
- the state of a KNX object
- the state of a BACnet object
Sequence control configuration
Activation of sequence control
The activation of sequence control is to be done for each motor line.
Sequence control configuration
The function for the sequence control is to be configured for each
motor line
1.
None -
This motor line does not use sequence control
2.
Open -
This motor line must wait for a “result” before opening
3.
Close -
This
motor line must wait for a “result” before closing
Sequence control configuration
– motor line
1.
Sequential control position limit
the max position the motor line is allowed to have without the
„result“ is being fulfilled.
For MotorLink
®
motor lines stepless variable.
For ±24 Volt motor lines 0 or 100%
2.
Sequential control with (upon what should the motor line wait?)
1. Motor line.
2. Local input
3. The state of a KNX object
4. The state of a BACnet object
3.
Sequential control with No
Upon which number should the motor line wait
4.
Sequential control position logic
In which positions should the sequential control be active
14.10
Magnetic clamp (magnetic door retainer)
Motor lines (only ±24 Volt motor output) can be defined as magnetic clamps.
Per panel up to max. 6A for WSC 320 and max. 3A for WSC 310 can be used for magnetic clamps, the remaining 14A and 7A
respectively are reserved for motors.
If a motor line is defined as magnetic clamp there will be power on the output as long as the panel is not triggered in fire condition.
If a motor line is defined as a magnetic clamp there will be no need of cable monitoring, as a cable error will have the same function
as fire condition. The cable monitoring can be selected if an error on the cables is to be shown.
Note, in case of mains power failure, the output will also loose its power and the magnetic clamp will release the door.
Technical data:
-
Power consumption per magnetic clamp: minimum 5mA
-
Current for magnetic clamp: maximum 6A for WSC 320 and maximum 3A for WSC 310