Configuration of local input X3 and X4
Input X3 and X4 on WCA 3SP and X1-X10 on WCA 8KI (binary)
If local inputs are connected on the card/cards WCA 3SP and/or
WCA 8KI, it/they shall be configured in:
1.
Input type: informs the
type of the input “Binary) (not to be
configured)
2.
Control smoke zones
*
2.1
Function in controlled smoke zones
(displayed only
if ‘Control smoke zones‘ is selected)
3.
Control motor groups
*
3.1
Function in controlled motor groups
3.2
Short output function
4.
Active state
5.
Thresholds configuration
*
The input can either control smoke zones or motor groups. When
one is selected the other option will disappear from the touch
screen.
The appendix contains all the items that can be configured - see
appendix for detailed explanation.
Configuration of local input X8 on
the WCA 3SP card
Input X8 on WCA 3SP (24V/48V) (primary used in France)
If there is connection in X8 on the card WCA 3SP, it shall be
configured in:
1.
Input type informs the type “24/48V”
(not to be configured)
2.
Control smoke zones
2.1
Function in controlled smoke zones (displayed only
if ‘Control smoke zones‘ is selected)
3.
Active state
The appendix contains all the items that can be configured - see
appendix for detailed explanation.
14.6.3 Usage of wind/rain sensors - WLA 33x
Usage of wind/rain sensors WLA 33x with motor groups (MG):
The used input e.g. S1
X10.5 is configured to “Control motor groups”,
the groups are chosen.
Then, in the menu “Active function in controlled motor groups” the
function “Safety” is selected.
Then, a function for the motor group when inactive can be selected
“Inactive function in the controlled motor groups”.
By each motor group it is possible to define the max opening for
“Safety”, meaning it is possible to allow windows and louvers inside
the build
ing to open despite “Safety” (wind/rain).
Facade windows, which are allowed to open e.g. 10%, to open
despite it rains.
Input shall be configured in:
Configuration of local input
1.
In the motor groups configure the input with the function “Safety“.
2. Configure the motor groups when anything else than close (0%) is
desired.
Note: motor groups also receive “Safety” signals from the smoke
zones they are associated with, see below for further information.