26
X11
For connection of master / slave connection via WSK-
Link™.
Data:
11.1 24V IN
11.2 Communication IN
11.3 0V IN
On the master panel, either input X5 or X6
– the inputs also used for break glass units - are used for the
connection. On the slave panel, the connection is done via X11.
It is possible to connect several panels in a master slave connection. However, the max total number of panels
AND break glass units on the bus must not exceed 10 units. The max cable length between two units must not
exceed 200m, see examples below, for how to connect the panels.
Smoke panel #2 and #3 are both master and slave panels.