When panels are physically connected through the WSK-
Link™ (the Master/Slave connection), safety signals and weather data
signals are automatically distributed among the connected panels.
Use the [ -
] button in the “Local Input” menu to associate Motor Groups with a Safety signal coming from the WSK-Link™.
All Motor Groups are associated with this signal as a default.
All smoke zones are automatically associated with the safety signal, this include smoke zones, which are independent from the
master-slave setup. If a motor group associated with a smoke should not react to safety signals, you have to configure the
motor group with “Use ’Safety’ from Smoke zone” = ‘No’ “.
Select “From WSK-Link™” in the “Weather” “Sensor type” menu to be able to use wind speed and wind direction signals coming
from the Master panel.
Configuration of Master
– Slave system:
A connected slave panel is shown on the master
panel’s touch screen.
When two panels are connected to each other in a master-slave
connection, the slave panel will appear as a green break glass unit
on the master’s touch screen.
Connected panels (#1) are always shown before connected break
glass units (#2 & #3).
The slave panel
’s appearance on
the master panel
On the master’s touch screen the Device type of the slave will
appear as a WSC 3xx.