47
Configuration of master slave connection
on master panel
To associate the slave panel with a smoke zone enter the smoke
zone on the master panel.
The associated smoke zone on the slave panel
The smoke zone will immediately be sent to the slave panel.
Components
– break glass units, comfort key pads etc. – connected to the slave panel are configured in the same way
components connected to the master or a normal panel.
All signals from components connected to the slave panel are automatically sent to the master panel, which then sends
commands (smoke, comfort and safety) back to the slave panel. The slave panel only react to commands from their master,
never from its local signals.
Signals from slaves and the master’s own connected components are treated on equal terms.
To get the fastest response, it is recommended that break glass units are connected to the master.
14.12
Network
For configuring network addresses.
The WCA 3SP card has a 10/100Mbit Ethernet connection. The connection support DHCP or static IP address as well as
Gateway
It is possible to configure different power consumption profiles for the Ethernet connection. To burden the 72 hours back-up
batteries as little as possible, use the setting ‘Off’ or ‘Auto’ (factory setting).
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Network is used in with BACnet IP interface
– contact WindowMaster for further information.
Network shall be configured in:
Configuration of ’Network’
1. DHCP
2. Power setting
The appendix contains all the items that can be configured - see
appendix for detailed explanation.