57
The smoke ventilation panel will signal fault on the batteries if the battery voltage is below 17V.
Within the framework of the service, they have to be replaced after the specified
maximum 4
year operating period.
Dispose of used batteries according to the National regulation.
CAUTION:
RISK OF EXPLOSION IF BATTERIES ARE REPLACED BY AN INCORRECT TYPE.
We recommend that the software of the panel is updated during the annual maintenance check!
The expected minimum lifetime for the
CompactSmoke™ is 10 years excluding the batteries.
22.1 Maintenance agreements
Be aware that regular inspection of smoke ventilation systems is a legal requirement. The legislation requires that the smoke
ventilation system's owner inspects and tests the system once every year.
WindowMaster offer maintenance agreements for the smoke ventilation system and every year we inspect the complete system
to ensure it complies with the applicable legislation. Maintenance of the smoke ventilation system includes checking windows,
window actuators and emergency power and checking that triggering and control functions are fully functional.
Contact our service department for further information:
tel44 1536 61 4070 or [email protected]
22.2 Replacement cards
22.2.1 Replacement of 3M8 and 3KI cards
1. Disconnect the 230 V and the batteries.
2. Wait until the display has completely turned off before removing the card.
3. Insert the replacement card.
4. Turn on the 230 V and connect the batteries.
5. The system will be ready again after approx. 2 seconds.
22.2.2 Replacement of 3SP card
1. Save a backup of the configuration on a USB stick (recommended).
2. Disconnect the 230 V and the batteries.
3. Wait until the display has completely turned off before removing the card.
4. Insert the 3PS replacement card.
5. Insert the USB stick into the new card.
6. Turn on the 230 V and connect the batteries.
7. Load the parameters from the USB stick
8. The system will be ready again after approx. 2 seconds.
If the WCA 3SP card, which is to be replaced, is completely without function then go straight to point 2.
If there is no backup of the configurations, these are to be entered manually.
It is therefore recommended to take a backup, on a USB stick, when the panel is running, if necessary please see section 14.14.
23
Declaration of Conformity and Declaration of Perfomance
The smoke ventilation panels are manufactured and tested accordingly to the European requirements.
The total system is not to be put into service until a declaration of conformity for the total system has been made.
The “Declaration of Conformity” and the EN certificate are supplied with panel as separate documents.