Fieldbus (KNX and BACnet)
Only when an Fieldbus card with a fieldbus interface is added to the smoke panel will the menus associated with the vairious
fieldbus options be shown.
Fieldbus example
An optional card with fieldbus interface is added to the panel and
the menus (e.g. configuration) now includes KNX and BACnet.
When the Fieldbus card is mounted a set of KNX or BACnet objects are available for each motor line, motor group and smoke
zone, which provides the options for status and commands.
Status objects
E.g. actual position, fault and operation status and the max opening angle (degrees).
Command objects
E.g. target position commands with different priority and MotorLink
®
motor speed.
Fieldbus link - "Conn. 1-10 "
The KNX or BACnet has also 10 configurable binary communication objects.
These can either be used for sending comfort commands to one or more motor groups or to give selected status from smoke zones
or motor groups.
See "KNX Application Program Description or "BACnet PICS” on the home pages (www.windowmaster.com) for further information
on available KNX or BACnet communication objects.
14.16.1
KNX configuration
KNX bus overview
– object configuration
Overview of the KNX objects.
For each KNX object a direction must be configured
-
None
-
Input
-
Output
When objects are configured as inputs or outputs, the controlled
motor group or smoke zone as well as its function must also be
configured.
KNX bus shall be configured in:
For all the objects the Power setting for the KNX bus must be
configured.