Some of the functions referrers to ‘Line’
The % value for the lines is configurable for each smoke zone. This is done in ‘View all details’. Furthermore, in “View all details”
– “Smoke zone” Line E and Line F can be given the highest priority, this is only used for fireman’s override panels.
Line
%
Function
Used for
A
100%
open
break glass unit
B
100%
open
smoke detector
(Switzerland: the value is often set to 0%, thus the windows will close
when smoke)
C
100%
open
D
0%
close
E
100%
open
F
0%
close
Reset
if this is selected the chosen function(s) will be reset
Number of smoke detectors to give an alarm:
If it is selected, that the alarm is only triggered when more smoke detectors give alarm, the smoke detectors are to be
connected to separate break glass unit
– see drawing:
14.6 Local input
The smoke control unit has nine inputs on the main control card. If further inputs are needed, the input card WCA 8KI (requires
the motor line card) can be added. This card has ten local inputs.
The touch screen has an overview of the local inputs.
14.6.1 Numbering of local inputs
All local inputs are numbered.
The number of the input depends on its location on a card - see overview below.
Smoke ventilation panel with input card