30
11
Cable monitoring of actuators
Actuators with MotorLink
®
are monitored by data communication.
When using ±24V standard actuators
either diodes or 10kΩ resistors can be used for cable monitoring, see below.
Configuration of cable monitoring with ±24V actuators
Configuration of cable monitoring
10kΩ-resistors (WSA 510)
– monitors ever single core for
interruption. Works with all WindowMaster actuators (default setting).
Diodes (WSA 432
)
– monitors every single core for interruption.
Works with all WindowMaster actuators.
10kΩ- resistors, simple (WSA 510)
– monitors for interruption on the
entire cable. Works with all WindowMaster actuators and most non-
WindowMaster actuators.
11.1 Usage of non-WindowMaster actuators
When using non-WindowMaster actuators
the cable monitoring ist set to ”simple”’.
Confi
guration of cable monitoring with non-WindowMaster actuators
Configuration of cable monitoring
If cable monitoring of non-WindowMaster® actuators connected to the
CompactSmoke™ is required the cable monitoring type is set to
”simple”.
12
Back-up batteries
Connect 2 pcs. back-up batteries type
WSC 007 for WSC 310 and type WSA 012
for WSC 320.
See section 22
“Maintenance” for further information.
Example of WSC 310 panel with back
–up batteries.