Remote control can be configured in:
Configuration of remote control
To enable remote control of the panel it is necessary to allow remote
control. This is done in the configuration of the system.
Identification of the IP-address
IP-
address of the CompactSmoke™
Screen shot from the PC when controlling
the
FlexiSmoke™ remotely
Start the ’WMaFlexiSmokeRemote program’ on the connected PC.
Enter the IP-address
and press ’Connect’.
21
Commissioning and test run
In case of hardware error, please see chapter 18
“The menu ‘Hardware error’”
The break glass unit WSK 50x will only give an acoustic fault signal if the door on the break glass unit is closed or if the door
contact on the break glass unit is pressed.
We recommend that the software of the panel is updated during the annual maintenance check!
We recommend that the commissioning of the smoke panel should be done by a competent smoke ventilation controls installer.
21.1 The control ventilation panel is completely installed, without the operating
voltage applied
a) Check all mechanical and electrical components for damage.
b) Check all screw and plug connections for tightness and/or firm seating
c) Check that all external components are installed:
1) ±24V actuators: Is the motor end module inserted in the last or only actuator?
2) Automatic smoke detectors: Is the passive end module inserted in the last or only smoke detector?
21.2 With mains voltage, without accumulator
Adhere to the relevant regulations!
Connect the mains cables and reapply the mains voltage.