Logical Command and Speed Reference
7-8 | CFW300
7
7.2.3 Parameters for Frequency Reference
P121 - Frequency Reference via HMI
Adjustable
Range:
0.0 to 400.0 Hz
Factory
Setting:
3.0 Hz
Properties:
Description:
Parameter P121 stores the frequency reference via HMI (P221 = 0 or P222 = 0). When the keys and
are
active and the HMI in the monitoring mode, the value of P121 is increased and shown on the HMI main display.
Besides, the P121 is used as input for the reference backup function.
NOTE!
The maximum setting value of parameter P121 via HMI is limited by P134 and P133.
P122 - Frequency Reference for JOG
Adjustable
Range:
-400.0 to 400.0 Hz
Factory
Setting:
5.0 Hz
Properties:
Description:
During the JOG command, the motor accelerates up to the value defined in P122, following the acceleration
ramp set according to P105. This command may be activated by any of the sources, as per
SELECTION FOR LOGICAL COMMAND AND FREQUENCY REFERENCE on page 7-1
. The negative values
determine a direction of rotation opposite to that defined by the inverter command word.
P124 - Multispeed Reference 1
Adjustable
Range:
-400.0 to 400.0 Hz
Factory
Setting:
3.0 Hz
P125 - Multispeed Reference 2
Adjustable
Range:
-400.0 to 400.0 Hz
Factory
Setting:
10.0 (5.0) Hz
P126 - Multispeed Reference 3
Adjustable
Range:
-400.0 to 400.0 Hz
Factory
Setting:
20.0 (10.0) Hz
P127 - Multispeed Reference 4
Adjustable
Range:
-400.0 to 400.0 Hz
Factory
Setting:
30.0 (20.0) Hz
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...