Logical Command and Speed Reference
7-4 | CFW300
7
P220 - Local/Remote Selection
Adjustable
Range:
0 = Always Local
1 = Always Remote
2 and 3 = Not Used
4 = Digital Input (DIx)
5 = Serial/USB (LOC)
6 = Serial/USB (REM)
7 and 8 = Not Used
9 = CO/DN/DP (LOC)
10 = CO/DN/DP (REM)
11 = SoftPLC
Factory
Setting:
0
Properties:
cfg
Description:
It defines the command origin source which will select between Local situation and Remote situation, where:
LOC:
means Local situation default.
REM:
means Remote situation default.
DIx:
according to function programmed for digital input in P263 to P266.
CO / DN / DP:
CANopen, DeviceNet or Profibus DP Interface.
P221 - Frequency Reference Selection - LOCAL Situation
P222 - Frequency Reference Selection - REMOTE Situation
Adjustable
Range:
0 = HMI
1 = AI1
2 = AI2
3 = Not Used
4 = Frequency Input (FI)
5 = AI1 + AI2 > 0
6 = AI1 + AI2
7 = E.P.
8 = Multispeed
9 = Serial/USB
10 = Not Used
11 = CO/DN/DP
12 = SoftPLC
13 = Not Used
14 = AI1 > 0
15 = AI2 > 0
16 = Not Used
17 = FI > 0
Factory
Setting:
P221 = 0
P222 = 1
Properties:
cfg
Description:
These parameters define the origin source for the frequency reference in the Local situation and Remote situation.
Some comments on the options of this parameter:
AIx:
it refers to the analog input signal according to
Section 12.1 ANALOG INPUTS on page 12-1.
HMI:
the reference value set by the keys and are contained in parametere P121.
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...