VVW Vector Control
10-4 | CFW300
10
P399 - Motor Rated Efficiency
Adjustable
Range:
50.0 to 99.9 %
Factory
Setting:
67.0 %
Properties:
cfg, V VW
Description:
This parameter is important for the precise operation of the V VW control. A misconfiguration will cause incorrect
calculation of the slip compensation, reducing the performance of the speed control.
P400 - Motor Rated Voltage
Adjustable
Range:
0 to 240 V
Factory
Setting:
According
inverter
model
Properties:
cfg, V VW
Description:
Set according to the data on the motor nameplate and the wire connection on the motor terminal box. This
value cannot be above the rated voltage value set in P296 (power supply rated voltage).
Table 10.2:
Default setting of P400 according to the identified inverter model
P296
P145 (Hz)
P400 (V)
0
Reserved
Reserved
1
50.0
230
60.0
220
2
50.0
230
60.0
220
For further information on model identification, refer to
of
OF THE INVERTER MODEL AND ACCESSORIES on page 6-1
.
P401 - Motor Rated Current
Adjustable
Range:
0.0 to 40.0 A
Factory
Setting:
1.0 x I
nom
Properties:
cfg
P402 - Motor Rated Speed
Adjustable
Range:
0 to 30000 rpm
Factory
Setting:
1720
(1310) rpm
Properties:
cfg
P403 - Motor Rated Frequency
Adjustable
Range:
0 to 400 Hz
Factory
Setting:
60 Hz
(50 Hz)
Properties:
cfg
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...