Quick Reference of Parameters, Alarms and Faults
CFW300 | 0-13
Param.
Description
Adjustable Range
Factory Setting
Prop.
Page
SoftPLC Parameter Configuration for PID Controller Application (P903 = 1)
P910
PID Controller Application Version
0.00 to 90.00
ro
P911
Control Setpoint
-9999 to 9999 [SPLC Eng. Un.]
200
rw
P912
Control Setpoint 1
-9999 to 9999 [SPLC Eng. Un.]
200
P913
Control Setpoint 2
-9999 to 9999 [SPLC Eng. Un.]
230
P914
Control Setpoint 3
-9999 to 9999 [SPLC Eng. Un.]
180
P915
Control Setpoint 4
-9999 to 9999 [SPLC Eng. Un.]
160
P916
Control Process Variable
-9999 to 9999 [SPLC Eng. Un.]
ro
P917
PID Controller Output
0.0 to 100.0 %
ro
P918
PID Controller Setpoint in Manual
Mode
0.0 to 400.0 Hz
0.0 Hz
P919
PID Controller Logical Status
Bit 0 = Sleep Mode Active (A750)
Bit 1 = PID in Manual (0) /
Automatic (1)
Bit 2 = PV Low Level (A760)
Bit 3 = PV Low Level (F761)
Bit 4 = PV High Level (A762)
Bit 5 = PV High Level (F763)
Bit 6 to 15 = Reserved
ro
P920
Selection of the Control Setpoint
Source
0 = Control Setpoint via HMI or
Communication Networks (P911)
1 = Control Setpoint via Analog
Input AI1
2 = Control Setpoint via Analog
Input AI2
3 = Control Setpoint via
Electronic Potentiometer (EP)
4 = Two Setpoints via Digital
Input DI3 (P912 and P913)
5 = Three Setpoints via Digital
Inputs DI3 and DI4 (P912, P913
and P914)
6 = Four Setpoints via Digital
Inputs DI3 and DI4 (P912, P913,
P914 and P915)
0
cfg
P921
Selection of the Control Process
Variable Source
1 = Control Process Variable via
Analog Input AI1
2 = Control Process Variable via
Analog Input AI2
3 = Control Process Variable via
Difference between Analog Input
AI1 and AI2
1
cfg
P922
Minimum Sensor Level of the
Control Process Variable
-9999 to 9999 [SPLC Eng. Un.]
0
P923
Maximum Sensor Level of the
Control Process Variable
-9999 to 9999 [SPLC Eng. Un.]
400
P924
Value for Low Level Alarm for the
Control Process Variable;
-9999 to 9999 [SPLC Eng. Un.]
100
P925
Time for Low Level Fault for the
Control Process Variable
0 to 9999 s
0 s
P926
Value for High Level Alarm for the
Control Process Variable
-9999 to 9999 [SPLC Eng. Un.]
350
P927
Time for High Level Fault for the
Control Process Variable
0 to 9999 s
0 s
P928
Selection of the PID Controller
Control Action
0 = Disable PID Controller
1 = Enable PID Controller in
Direct Mode
2 = Enable PID Controller in
Reverse Mode
0
cfg
P929
PID Controller Operation Mode
0 = Manual
1 = Automatic
2 = Select Control to Manual (0)
or Automatic (1) via digital input
DI2
2
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...