Functions Common to All the Control Modes
11-4 | CFW300
11
P149 - Compensation of the DC Link Voltage
Adjustable
Range:
0 = Inactive
1 = Active
Factory
Setting:
0
Properties:
cfg
Description:
It enables the use of Compensation of the DC link.
P150 - Type DC V/f Link Regulator
Adjustable
Range:
0 = Hold_Ud and Decel_LC
1 = Accel_Ud and Decel_LC
2 = Hold_Ud and Hold_LC
3 = Accel_Ud and Hold_LC
Factory
Setting:
0
Properties:
cfg
Description:
P150 configures the behavior of the ramp for the limitation functions of the DC Link Voltage and Current Limitation.
In those cases, the ramp ignores the reference and takes an action of accelerating (accel), decelerating (decel)
or freezing (hold) the normal path of the ramp. That occurs because of the limit pre-defined in P151 and P135
for the DC Link (Ud) Limitation and for Current (LC) Limitation, respectively.
P151 - DC Link Regulation Level
Adjustable
Range:
348 to 460 V
Factory
Setting:
According to
Properties:
Description:
Voltage level to activate the DC link voltage regulation.
Table 11.1:
Actuation Level of the Voltage Regulation
Input Voltage
P151 Actuation Band
P151 Factory Default
100 to 127 Vac
391 to 460 Vdc
395 Vdc
200 to 240 Vac
348 to 410 Vdc
365 Vdc
shows the block diagram of the actuation of the limitation.
and
show the example chart.
Ramp
Reference
Output frequency
error
≥ 0
+
-
hold
t
P001
P004
P151
P002
P100-P104
Figure 11.2:
Block diagram DC Link voltage limitation
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...