0
Quick Reference of Parameters, Alarms and Faults
CFW300 | 0-9
Param.
Description
Adjustable Range
Factory Setting
Prop.
Page
P407
Motor Rated Power Factor
0.50 to 0.99
0.69
cfg, V V W
P408
Run Self-Tuning
0 = No
1 = Yes
0
cfg, VVW
P409
Stator Resistance
0.01 to 99.99 Ω
According to
inverter model
cfg, V V W
P510
Unit SoftPLC Eng.
0 = Without Unit
1 = A
2 = V
3 = Hz
4 = s
5 = %
6 = ºC (°F)
7 = rpm
P511
SoftPLC Indication Form
0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
1
P580
Fire Mode Configuration
0 = Inactive
1 = Active
2 = Active / P0134
3 = Reserved
4 = Active / Gen. Disable
0
cfg
P582
Auto-reset configuration
0 = Limited
1 = Unlimited
0
cfg
P588
Energy Saving Max. Torque
0 to 85 %
0
cfg, V/f
P589
Level of Minimum Applied Voltage
40 to 80 %
40 %
cfg, V/f
P590
Energy Saving Minimum
Frequency
12.0 Hz to 400.0 Hz
20.0 Hz
cfg, V/f
P591
Energy Saving Hysteresis
0 to 30 %
10 %
cfg, V/f
P613
Software Revision
-9999 a 9999
According to
Software revision
ro
P680
Logical Status
0 to FFFF (hexa)
Bit 0 = Reserved
Bit 1 = Run Command
Bit 2 = Fire Mode
Bit 3 and 4 = Reserved
Bit 5 = 2
nd
Ramp
Bit 6 = Config. Status
Bit 7 = Alarm
Bit 8 = Running
Bit 9 = Enabled
Bit 10 = Forward
Bit 11 = JOG
Bit 12 = Remote
Bit 13 = Undervoltage
Bit 14 = Reserved
Bit 15 = Fault
ro
P681
Speed in 13 bits
0 to FFFF (hexa)
ro
P682
Serial/USB Control
0 to FFFF (hexa)
Bit 0 = Ramp Enable
Bit 1 = General Enable
Bit 2 = Run Forward
Bit 3 = JOG Enable
Bit 4 = Remote
Bit 5 = 2
nd
Ramp
Bit 6 = Reserved
Bit 7 = Fault Reset
Bit 8 to 15 = Reserved
ro
P683
Serial/USB Speed Ref.
0 to FFFF (hexa)
ro
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...