Programming Basic Instructions
CFW300 | 5-5
5
5.3 SITUATIONS FOR CONFIG STATUS
The Config status is indicated by the HMI "ConF" status, as well as in parameters P006 and P680. Such status
indicates that the CFW300 cannot enable the output PWM pulses because the inverter configuration is incorrect
or incomplete. For further details about indications of Config state on the HMI, refer to
P047 - Estado CONF
Adjustable
Range:
0 a 999
Factory
Setting:
Properties:
ro
Description:
The table below shows the situations of Config status, where the user can identify the origin condition through
parameter P047.
Table 5.3:
Situations for Config status
P047
Condition
0
Out of CONFIG status. The HMI and parameters P006 and P680 must not indicate ConF
1
Two or more DIx (P263...P270) programmed for (4 = Forward Run)
2
Two or more DIx (P263...P270) programmed for (5 = Reverse Run)
3
Two or more DIx (P263...P270) programmed for (6 = Start)
4
Two or more DIx (P263...P270) programmed for (7 = Stop)
5
Two or more DIx (P263...P270) programmed for (8 = Direction of Rotation)
6
Two or more DIx (P263...P270) programmed for (9 = LOC/REM)
7
Two or more DIx (P263...P270) programmed for (11 = Accelerate E.P.)
8
Two or more DIx (P263...P270) programmed for (12 = Decelerate E.P.)
9
Two or more DIx (P263...P270) programmed for (14 = 2
nd
Ramp)
10
Reserved
11
Two or more DIx (P263...P270) programmed for (24 = Disable Flying Start)
12
Two or more DIx (P263...P270) programmed for (26 = Programming Off)
13
Reserved
14
Reserved
15
DIx (P263...P270) programmed for (4 = Forward Run) without DIx (P263...P270) programmed for (5 = Reverse Run) or the
opposite
16
DIx (P263...P270) programmed for (6 = Start) without DIx (P263...P270) programmed for (7 = Stop) or the opposite
17
P221 or P222 programmed for (8 = Multispeed) without DIx (P263...P270) programmed for (13 = Multispeed) or the opposite
18
P221 or P222 programmed for (7 = E.P.) without DIx (P263...P270) programmed for (11 = Accelerate E.P) or the opposite
19
P224 programmed for (1 = DIx)
OR
P227 programmed for (1 = DIx) without DIx (P263...P270) programmed for (1 = Run/Stop)
AND
without DIx (P263...P270) programmed for (2 = General Enable)
AND
without DIx (P263...P270) programmed for (3 = Quick
Stop)
AND
without DIx (P263...P270) programmed for (4 = Forward Run)
AND
without DIx (P263...P270) programmed for
(6 = Start)
20
Reserved
21
P221 or P222 programmed for (8 = Multispeed) with DI1 (P263)
AND
DI2 (P264)
OR
DI1 (P263)
AND
DI5 (P267)
OR
DI1 (P263)
AND
DI6 (P268)
OR
DI2 (P264)
AND
DI5 (P267)
OR
DI2 (P264)
AND
DI6 (P268)
OR
DI5 (P267)
AND
DI6 (P268) programmed
for (13 = Multispeed)
22
Minimum Frequency Reference (P133) greater than Maximum Frequency Reference (P134)
29
Two or more DIx (P263...270) programmed for (49 = Enable Fire Mode)
OR
two or more DOx (P275...P278) Programmed for
(45 = Fire Mode
OR
P580 programmed for 1, 2 or 4 (Fire Mode Enabled) without DIx programmed for (49 = Enable Fire Mode)
OR
Dix programmed for (49 = Enable Fire Mode)
OR
Dox programmed for (47 = Fire Mode) and P580 programmed for
(0 = Fire Mode Disabled) or (3 = Reserved)
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...