VVW Vector Control
CFW300 | 10-5
10
P404 - Motor Rated Power
Adjustable
Range:
0 = 0.16 HP (0.12 kW)
1 = 0.25 HP (0.18 kW)
2 = 0.33 HP (0.25 kW)
3 = 0.50 HP (0.37 kW)
4 = 0.75 HP (0.55 kW)
5 = 1.00 HP (0.75 kW)
6 = 1.50 HP (1.10 kW)
7 = 2.00 HP (1.50 kW)
8 = 3.00 HP (2.20 kW)
9 = 4.00 HP (3.00 kW)
10 = 5.00 HP (3.70 kW4)
Factory
Setting:
According
inverter
model
Properties:
cfg, V VW
Description:
The setting of parameters P401, P402, P403 and P404 must be according to the data on the nameplate of the
motor used, taking into account the motor voltage.
The setting of parameter P402 via HMI for values above 9999 rpm is performed from 10.00 to 30.00 rpm (x 1000).
P405 - Encoder Pulse Number
Adjustable
Range:
32 to 9999 ppr
Factory
Setting:
1024
Properties:
cfg
Description:
It sets the number of pulses per revolution (ppr) of the incremental encoder. This parameter influences the
indication of the speed parameters (P038) and pulse counter (P039) of the encoder.
NOTE!
Parameter P405 is only visible on the HMI if the CFW300-IOAENC expansion module is connected
to the inverter.
P407 - Motor Rated Power Factor
Adjustable
Range:
0.50 to 0.99
Factory
Setting:
0.69
Properties:
cfg, V VW
Description:
The setting of this parameter must be according to the data on the nameplate of the motor used, taking into
account the motor voltage.
P408 - Self-Tuning
Adjustable
Range:
0 = No
1 = Yes
Factory
Setting:
0
Properties:
cfg, V VW
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...