0
Quick Reference of Parameters, Alarms and Faults
0-6 | CFW300
Param.
Description
Adjustable Range
Factory Setting
Prop.
Page
P252
(*)
AO1 Output Gain
0.000 to 9.999
1.000
P253
(*)
AO1 Output Signal
0 = 0 to 10 V
1 = 0 to 20 mA
2 = 4 to 20 mA
3 = 10 to 0 V
4 = 20 to 0 mA
5 = 20 to 4 mA
0
P254
(*)
AO2 Output Function
See Options in P251
5
P255
(*)
AO2 Output Gain
0.000 to 9.999
1.000
P256
(*)
AO2 Output Signal
See Options in P253
0
P263
DI1 Input Function
0 = Not Used
1 = Run/Stop
2 = General Enable
3 = Fast Stop
4 = Forward Run
5 = Reverse Run
6 = Start
7 = Stop
8 = Direction of Rotation
9 = LOC/REM
10 = JOG
11 = Increase E.P.
12 = Decelerate E.P.
13 = Multispeed
14 = 2
nd
Ramp
15 to 17 = Not Used
18 = No Ext. Alarm
19 = No Ext. Fault
20 = Reset
21 to 23 = Not Used
24 = Disab. Flying Start
25 = Not Used
26 = Lock Prog.
27 to 31 = Not Used
32 = 2
nd
Ramp Multispeed
33 = 2
nd
Ramp E.P. Ac.
34 = 2
nd
Ramp E.P. De.
35 = 2
nd
Ramp FWD Run
36 = 2
nd
Ramp REV Run
37 = Turn ON / Ac. E.P.
38 = De. E.P. / Turn OFF
39 = Stop
40 = Safety Switch
41 = Application Function 1
42 = Application Function 2
43 = Application Function 3
44 = Application Function 4
45 = Application Function 5
46 = Application Function 6
47 = Application Function 7
48 = Application Function 8
49 = Activate Fire Mode
50 = Manual/Automatic PID
(Only DI2 for P903 = 1)
51 = Increase Setpoint
Command (PE) (Only DI3 for
P903 = 1)
52 = Decrease Setpoint
Command (Only DI4 for P903 = 1)
53 = 1st DI Control Setpoint
(Only DI3 for P903 = 1)
54 = 2st DI Control Setpoint
(Only DI4 for P903 = 1)
1
cfg
P264
DI2 Input Function
See Options in P263
8
cfg
P265
DI3 Input Function
See Options in P263
0
cfg
P266
DI4 Input Function
See Options in P263
0
cfg
P267
(*)
DI5 Input Function
See Options in P263
0
cfg
P268
(*)
DI6 Input Function
See Options in P263
0
cfg
P269
(*)
DI7 Input Function
See Options in P263
0
cfg
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...