Programming Basic Instructions
CFW300 | 5-3
5
Together with the unit in P209 and the decimal places in P210, the rated reference (P208) defines the speed
indication on the inverter HMI. According to the factory default of those parameters, the preset scale on the
inverter is in "Hz" and with a decimal place (60.0 Hz or 50.0 Hz). On the other hand, by setting P208 = 1800
or 1500, P209 = 7 and P210 = 0, a scale in "rpm" with no decimal places is defined (1800 rpm or 1500 rpm).
P209 - Reference Engineering Unit
Adjustable
Range:
0 and 1 = Without Unit
2 = V
3 = Hz
4 = Without Unit
5 = %
6 = Without Unit
7 = rpm
Factory
Setting:
3
Properties:
Description:
This parameter selects the engineering unit that will be presented on parameters P001 and P002.
P210 - Reference Decimal Point
Adjustable
Range:
0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
Factory
Setting:
1
Properties:
Description:
This parameter allows setting the form of indication of parameters P001 and P002.
P213 - Bar Graph Scale Factor
Adjustable
Range:
1 to 9999
Factory
Setting:
1 x I
nom
Properties:
Description:
This parameter configures the full scale (100 %) of the bar graph to indicate the parameter selected by P207.
P842 - Quick View 1 IR
P843 - Quick View 2 IR
Adjustable
Range:
0 to 959
Factory
Setting:
P842 = 2
P843 = 375
Properties:
Description:
These parameters define which parameters (their respective values) will be viewed by using the
of the
infrared remote control (available with the accessory CFW300-IOADR).
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...