SoftPLC
17-2 | CFW300
17
Figure 17.1:
Description of the parameter P903 options
P903
Description
0
It defines that the application that will run on the SoftPLC is the one loaded by the user through the ladder programming tool
1
It defines that the application that will run on the SoftPLC is the PID controller
ATTENTION!
It is recommended to load the factory setting (P204 = 5 or 6) after alternating between user's application
and PID controller application.
P904 - Action for Application not Running
Adjustable
Range:
0 = Inactive
1 = Generate Alarm
Factory
Setting:
0
Properties:
cfg
Description:
It defines which action will be taken by the product in case the SoftPLC not running condition is detected, and
it may generate alarm A708 (1), fault F709 (2) or neither of the previous actions, remaining inactive (0).
P910 to P959 - SoftPLC Parameters
Adjustable
Range:
-9999 to 9999
Factory
Setting:
0
Properties:
Description:
These are parameters whose use is defined by the SoftPLC function.
NOTE!
Parameters P910 to P959 can only be viewed when there are application installed.
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...