Programming Basic Instructions
5-2 | CFW300
5
P200 - Password
Adjustable
Range:
0 = Inactive
1 = Active
2 to 9999 = New Password
Factory
Setting:
0
Properties:
cfg
Description:
It allows activating the password (by inserting a new value) or disabling it. For further details regarding the use
of this parameter, refer to
Table 5.1:
Required procedure for each kind of action
Action
Procedure
Activate password
1. Set P200 with the desired value for the password (P200 = password)
2. The setting is completed, the new password is active and P200 is automatically adjusted for 1 (password
active)
(1)
Change password
1. Set the current value of the password (P000 = password)
2. Set the desired value for the new password in P200 (P200 = new password)
3. The setting is completed, the new password is active and P200 is automatically adjusted for 1 (password
active)
(1)
Disable password
1. Set the current value of the password (P000 = password)
2. Set inactive password (P200 = 0)
3. The setting is completed, the password is disabled
(2)
Disable password
1. Activate a factory default by means of P204
2. The setting is completed, the password is disabled
(2)
(1)
It only allows changing the content of the parameters when P000 is equal to the value of the password.
(2)
It is allowed to change the content of the parameters and P000 is inaccessible.
P205 - Main Display Parameter Selection
Adjustable
Range:
0 to 999
Factory
Setting:
2
Properties:
Description:
This parameter defines which parameter will be viewed on the HMI when the motor is enabled after initialization.
P207 - Bar Graph Parameter Selection
Adjustable
Range:
0 to 999
Factory
Setting:
3
Properties:
Description:
This parameter defines which parameter will be shown on the HMI bar graph.
P208 - Reference Scale Factor
Adjustable
Range:
1 to 9999
Factory
Setting:
600 (500)
Properties:
Description:
This parameter allows adjusting the scale of the parameter speed reference P001 and output (motor) speed
P002 so as to convert the indication of frequency values applied to the motor (Hz) into angular speed in "rpm"
or a proportional value in "%", for instance.
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...