Alternate Fire Landing at Rear Opening
–
Turn this feature on to use the rear
opening at the alternate fire opening, instead of the front opening. If there is only one
opening at the alternate fire landing, then this feature will have no effect.
•
Disable Shunt Trip on Fire Service Phase 2
–
Turn this feature on to disable Shunt
Trip operation when the car is on Fire Service Phase 2.
•
Enable Shunt Trip on Inspection
–
Turn this feature on to enable Shunt Trip
operation when the car is on Inspection.
•
Disable ECReturn Latch on 2000 Fire Code
–
Turn this feature on to disable the
holding circuit on Fire Service Phase 2 Return on 2000 (or later) Code. This allows the
Return mode to be cancelled by turning the Fire Switch to t
he “On” position. Check the
appropriate code to see if this is required or allowed.
•
Fire Sensors are Normally Open Inputs
–
Turn this feature on if the Smoke Sensor
inputs are normally open on normal operation, and close when a fire is detected. The
default is to use Smoke Sensors that are closed on normal operation and open when a
fire is detected.
•
Code Blue Overrides Fire Service
–
Turn on to allow Code Blue (Medical Emergency)
to continue to operate on Fire Service. If this feature is not turned on, then Code Blue
will be overridden after about 25 seconds.
•
Allow Car Call Cancel if Running on EMT
–
Turn on to allow all car calls to be
cancelled if the EMT Car Switch is turned off while the car is running. This gives a means
to cancel car calls, but also requires that the EMT Car Sw be left ON until the car reaches
its destination.
•
Enable Pulsing Selector (off=Floor Sws)
–
Turn this feature on to enable a pulsing
floor selector, rather than individual Floor Switches. With a pulsing arrangement, there
is an up or a down pulse to change floors. Additionally at the terminal landings,
enabling the up pulse input and the door zone input will reset to the top landing, while
energizing the down pulse and door zone will reset the floor position to the bottom
landing.
•
Enable Separate Call I/O (4 Wire Calls)
–
Turn this feature on to enable separate
wiring for the inputs and outputs for the car and hall calls. If this feature is disabled
then the car and hall call inputs are connected to the corresponding outputs.
•
Enable Door Check Feature
–
Turn this feature on to enable the Door Check feature.
This allows the status of the Car Door and the Hall Doors to be checked according to the
appropriate codes.
•
Enable Redundancy Fault Checking
–
Turn this feature on to enable 2000 (or later)
code redundancy fault checking. This enables the redundancy fault timers, and checks
the leveling inputs and running inputs for stuck relays or contacts, according to the 2000
(or later) code.
•
Use Car Lantern outputs for Hall Lanterns
–
Turn this feature on to use the Car
Lantern outputs as Hall Lanterns. If there are only two landings, then the Hall Lanterns
can be connected directly to the Car Lantern outputs. If there are more than two
landings, then additional external relays are needed to enable the appropriate lantern at
each floor.
•
Do Not Run On Fire Service and BORIS
–
Turn this feature on to prevent the car
from running if Fire Service is enabled while on battery backup operation.