Virginia Controls, LLC
MH-3000 User Manual, 1_03C10-VC
Page 93
•
Enable Door Auto Close
–
Turn this feature on to enable the Automatic Door Close
outputs. The Door Close outputs and the appropriate external interface circuits for the
Door Operator must be provided for this feature to work. Unless additional features
affecting the Door Close output are energized, the Automatic Door Close output will be
energized on Fire Service Phase 1 (Hall) to close the doors and allow the car to return to
the designated landing.
•
Enable Door Auto Close from Car Buttons
–
Turn this feature on to allow the
automatic Door Close output to be energized when a Car Call Button is pressed.
•
Enable Door Auto Close from Hall Buttons
–
Turn this feature on to allow the
automatic Door Close output to be energized when a Hall Call Button is pressed.
•
Drop ESB with Door Open Limit
–
Turn this feature on to de-energize the ESB Stop
Switch Bypass output when the car has returned to the designated landing and opened
the doors.
•
Drop MF Output on Fire 2000 Code
–
Turn this feature on to allow the MF output to
de-energize if the car has returned to the designated fire landing, and is on shutdown.
With 2000 (or later) Fire Code, the doors should close under these circumstances.
•
Enable Shunt with Door Open Limit
–
Turn this feature on to enable the Shunt Trip
output when the Door Open Limit indicates the doors are open. If this feature is
disabled, the Shunt Trip output will come on shortly after the car stops, even if the doors
have not opened. This feature should only be enabled if there are power operated doors
that also have a Door Open Limit signal connected to the controller.
•
Enable Timed Door Open Fault in Fault Log
–
Turn this feature on to enable the
TDOPEN fault in the Fault Log. This feature should only be enabled with power operated
doors. If it is enabled with manual doors, then a fault will be logged every time the car
stops and the doors are not opened.
•
Enable Door Reopen for Courion Doors
–
Turn this feature on to enable the ECH
signal to the power operated doors when the car is on Fire Service and the Car Fire Sw
is turned from the Off position back to Hold or On. This is used with Courion door
operators to reopen the doors.
•
Enable 2007+ Fire Code for Manual Doors
–
Turn this feature on to allow Fire
Service Phase 2 (Car) to be initiated if the doors have been opened at the Main Ldg,
even though they may now be closed. This is in allowable in the 2007 and later Fire
Code.
•
Enable Door Close After Shutdown Return
–
Turn this feature on to make the doors
park closed after the car has returned on shutdown. Check the applicable codes to see if
this feature is required.
Features used with Triplex controllers only
•
DISPATCH FAILURE CALLS
•
Run to 1st Ldg on Dispatch Failure
–
Turn this feature on to make the car run to this
landing if it loses communication with the dispatcher. Set the desired calls to allow the
cars to provide service to the building if the dispatcher fails. The car will park with its
doors open if it has no registered calls, and the communication has failed.
•
Run to 2nd Ldg on Dispatch Failure
–
Turn this feature on to make the car run to this
landing if it loses communication with the dispatcher.