Virginia Controls, LLC
MH-3000 User Manual, 1_03C10-VC
Page 89
fault log clear of non-essential faults. The following faults will not be logged if this
feature is enabled: TDOPEN, TDCLOSE, TDOPN-R, TDCLO-R, CARSTUK, DRCONTS, OUT-
DZ, COMMFLT, FIRE, MRSMOKE, SHUNT, FLOOD
•
Flood Return Ldg is 3 (not 2)
–
Turn this feature on to make the car return to the
third landing from the bottom if Flood Service is initiated. The default floor is the second
floor from the bottom.
•
Flood Return Ldg is Top Ldg (not 2)
–
Turn this feature on to make the car return to
the top landing if Flood Service is initiated. The default floor is the second floor from the
bottom.
•
Flood overrides Independent, Attendant, Med Emerg
–
Turn this feature on to
allow Flood Service to override Independent Service, Attendant Operation and Medical
Emergency Operation. If this feature is not enabled, then the car will remain under the
control of the operator if the Flood Service input is energized.
•
Flood overrides Shutdown (Low Oil, Rev. Phase, etc)
–
Turn this feature on to
allow Flood Service to override shutdown functions that would normally return the car to
the bottom landing. The car will still not be able to run up, but Flood Service will remain
in effect even though a shutdown feature is in effect.
•
Do Not Run on Flood and BORIS
–
Turn this feature on to prevent the car from
running if Flood Service and BORIS Battery Backup operation are initiated at the same
time.
•
Do Not Run Down Below Main on Flood and Shutdown
–
Turn this feature on to
prevent the car from running if it is at or below the Main Floor and the car is on Flood
Service and Shutdown Operation.
•
Fire Service Overrides Flood Operation
–
Turn this feature on to allow Fire Service to
override Flood Service. The car will return to the Main Fire Floor, even if that is the
bottom landing.
•
Flood Operation Overrides Hall Fire Service
–
Turn this feature on to allow Flood
Service to override Fire Service, and cause the car to leave the bottom landing, even if
that is the designated Fire landing. If this feature is not set, then whichever feature
(Fire Service or Flood Service) is initiated first will take precedence.
•
Enable Car To Lobby Input
–
Turn on to enable the Car To Lobby Shutdown inputs.
The input for this feature must have been assigned for this feature to work properly.
•
Enable ES Input
–
Turn on to enable the ES (Emergency Stop Switch) Input. This is
normally used on a Duplex, or with MH5 Monitoring. The input for this feature must
have been assigned for this feature to work properly.
•
Disable DISC Input (BORIS is not used)
–
Turn on to disable BORIS operation.
•
Enable Shunt Trip Feature
–
Turn on to enable the Shunt Trip feature. The input and
output for this feature must have been assigned for this feature to work properly. This
feature can be turned off to disable the Shunt Trip if it was supplied, but is not required.
Shunt Trip operation can be accomplished externally to the controller, if desired.
•
Enable Low Oil Switch Feature
–
Turn on to enable the Low Oil Sw feature. The input
for this feature must have been assigned for this feature to work properly. This feature
can be turned off to disable the Low Oil Sw if it was supplied, but is not required. The
feature “
Enable Low Oil Switch or Oil Temp Feature
” must also be turned on, if provided.
•
Enable Oil Temperature Switch Feature
–
Turn on to enable the Oil Temperature Sw
feature. The input for this feature must have been assigned for this feature to work