Fault name
Panel
display
Troubleshooting
Troubleshooting
Countermeasures
Current
detection
failure
Err17
u
Whether the internal wiring of the
inverter is loose
u
Is the current detection device
normal?
u
Whether the main control board or
driver board is normal
u
Check the wiring
u
Seek technical support
Short to
ground fault
Err20
u
Motor short circuit to ground
u
Replace the cable or
motor
Input phase
loss fault
Err23
u
The three-phase input power supply
is abnormal
u
The driver board is abnormal
u
The lightning protection board is
abnormal
u
The main control board is abnormal
u
Check and eliminate
problems in peripheral
circuits
u
Seek technical support
Output
phase loss
fault
Err24
u
The lead wire from the inverter to
the motor is abnormal
u
The three-phase output of the
inverter is unbalanced when the
motor is running
u
The driver board is abnormal
u
Module exception
u
Eliminate peripheral
faults
u
Check whether the
three-phase windings
of the motor are normal
and troubleshoot
u
Seek technical support
read and
write failure
Err25
u
EEPROM chip damaged
u
Replace the main
control board
Parameter
Err27
u
Is the host computer working?
u
Is the communication connection
normal?
u
Whether the communication
parameter P8 group is correct
u
Check the wiring of the
host computer, etc.
u
Check the
communication wiring
u
Check the parameters
of P8 group
Parameter
Err28
u
Input external normally open or
normally closed fault signal through
multi-function DI terminal
u
Fault reset
Excessive
speed
deviation
Err29
u
The load is too heavy and the set
acceleration time is too short
u
The setting of fault detection
parameters P9-31 and P9-32 is
unreasonable
u
Extend the set
acceleration and
deceleration time
u
Reset P9-31 and P9-32
Chapter 9 Troubleshooting and Countermeasures
C
h
a
p
te
r
9
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...