-195-
Chapter 6 Description of Function Codes
Fig.6-22
Schematic diagram of over-current stall protection
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-08
Overvoltage stall allowable rise
limit value
0.0%
~
50.0%
10.0%
☆
The maximum allowable adjustment amount when adjusting the frequency when overvoltage
stalls, generally does not need to be modified.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-11
Fault automatic reset times
0
~
20
0
☆
P9-12
Fault relay action selection during
automatic fault reset
0
~
1
0
☆
After selecting the automatic fault reset function of the inverter, during the execution of fault
reset, it can be determined whether the fault relay action is required to shield the fault alarm
caused by this parameter setting, so that the equipment can continue to run.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-13
Fault automatic reset interval time 0.1s
~
100.0s
1.0s
☆
C
h
a
p
te
r
6
Output current
Overcurrent stall
protective current
Output frequency (Hz)
Time(t)
Time(t)
speed up
the process
constant
speed process
deceleration
process
Set frequency
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...