Chapter 6 Description of Function Codes
4: PULSE setting, refer to the setting instructions of function codes P5-30~P5-33;
100% corresponding to P3-23.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P3-23
Braking torque upper limit
0.0
~
200.0%
150.0%
☆
This parameter is used to set the upper limit of braking torque of the inverter. This parameter
is used to set the upper limit value of the motor torque of the inverter. When the actual directi-
on of the motor is the same as the direction of the torque, it is electric, otherwise it is braking.
When the electric torque and braking torque need different setting values, they can be set
separately through P3-21 and P3-23.
For example, in the case of cam load, due to the periodic change of the electric and braking
states, at this time, by appropriately reducing the upper limit of the braking torque P3-23, the
rise of the inverter bus voltage can be effectively reduced without affecting the normal operat-
ion of the driving load.
C
h
a
p
te
r
6
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...