-171-
Chapter 6 Description of Function Codes
Value
Function
Description
41
Reserved
Reserved
42
Reserved
Reserved
43
Frequency up to 2
Please refer to the description of function codes P7-57
and P7-58.
44
Current reaches 2
Please refer to the description of function codes P7-63
and P7-64.
45
Fault output (no
output under voltage)
When the inverter fails and it is not an undervoltage fault,
the ON signal is output.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P6-04
FM terminal output mode
selection
0~1
0
☆
P6-05
FMR output selection
0~45
0
☆
The FM terminal can be used as the high-speed pulse terminal FMP (P6-04=0) or as the op-
en-collector switch output terminal (P6-04=1). When FM terminal is used as FMP, its maxim-
um output frequency is set by P6-12, and its corresponding function output is set by P6-11.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P6-09
AO1 output selection
0~16
0
☆
P6-10
AO2 output selection
0
☆
P6-11
FMP output selection
0
☆
The output range of analog output AO1 and AO2 is 0V~10V, or 0mA~20mA.
The scale relationship between the range of analog output and the corresponding function is
shown in the following table:
Value
Function
Description
0
Running frequency
0
~
Maximum output frequency, that is, 100% corresponds to
the maximum frequency
1
Setting frequency
0
~
Maximum output frequency, that is, 100% corresponds to
the maximum frequency
C
h
a
p
te
r
6
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...