-187-
Chapter 6 Description of Function Codes
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-65
LED running display parameter 2
0x0~0x1PF
H.010
7 6 5 4 3 2 1 0
Bit00: Target torque% 0001
Bit01: Output torque% 0002
Bit02: Pulse input pulse frequency (KHz) 0004
Bit03: HDI input line speed (m/min) 0008
Bit04: Motor speed (rmp) 0010
Bit05: AC incoming line current (A) 0020
Bit06: Cumulative running time (h) 0040
Bit07: Current running time (min) 0080
15 14 13 12 11 10 9 8
Bit08:
Cumulative power consumption
(kWh) 0100
Bit09: Reserved
Bit10: Reserved
Bit11: Reserved
Bit12: Reserved
Bit13: Reserved
Bit14: Reserved
Bit15: Reserved
Figure 6-20. LED operation display bit map
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-67
AI1 input voltage lower limit
0.00V
~
P7-68
2.00V
☆
P7-68
AI1 input voltage upper limit
P7-67
~
11.00V
8.00V
☆
When the value of the analog input AI1 is less than P7-67, or the AI1 input is greater than
P7-68, the multi-function terminal of the inverter outputs the "AI1 input overrun" ON signal,
which is used to indicate whether the input voltage of AI1 is within the set range.
C
h
a
p
te
r
6
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...