Chapter 6 Description of Function Codes
-204-
Determines how strongly the PID regulator adjusts the deviation rate of change. The longer
the differentiation time, the greater the adjustment intensity. Differential time means that when
the feedback amount changes 100.0% within this time, the adjustment amount of the differen-
tial regulator is the maximum frequency.
Function
code
Name
Description
(setting range)
Factory
Default
Change
PA-09
PID reverse cutoff frequency
0.00
~
Maximum
frequency (P0-14)
0.00Hz
☆
In some cases, only when the PID output frequency is negative (that is, the inverter is revers-
ed), can the PID control the given amount and the feedback amount to the same state, but
too high reverse frequency is not allowed in some occasions Yes, PA-09 is used to determi-
ne the upper limit of the reverse frequency.
Function
code
Name
Description
(setting range)
Factory
Default
Change
PA-10
Deviation limit
0.0%
~
100.0%
0.0%
☆
When the deviation between the PID given amount and the feedback amount is less than
PA-10, the PID will stop adjusting. In this way, when the deviation between the given and the
feedback is small, the output frequency is stable and unchanged, which is very effective for
some closed-loop control occasions.
Function
code
Name
Description
(setting range)
Factory
Default
Change
PA-11
Differential clipping
0.00%
~
100.00%
0.0%
☆
In the PID regulator, the role of differential is more sensitive, and it is easy to cause system
oscillation. For this reason, the role of PID differential is generally limited to a small range.
PA-11 is used to set the range of PID differential output.
Function
code
Name
Description
(setting range)
Factory
Default
Change
PA-12
PID feedback filter time
0.00
~
60.00s
0.00s
☆
PA-12 is used to filter the PID feedback amount, which is beneficial to reduce the influence of
the feedback amount by interference, but it will bring the response performance of the proce-
ss closed-loop system.
C
h
a
p
te
r
6
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...