Chapter 6 Description of Function Codes
-196-
The waiting time between the fault alarm and the automatic reset of the fault.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-14
Input phase loss enable selection
0~1
1
☆
0: Disable.
1: Enable, the fault code is Err23 when input phase loss occurs.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-15
Output phase loss enable
selection
0.0%
~
50.0%
10.0%
☆
0: Disable.
1: Enable, the fault code is Err24 when output phase loss occurs.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-16
Power-on to ground short-circuit
protection selection
0.0%
~
50.0%
10.0%
☆
0: Disable
.
1: Enable, allow the inverter to detect whether the motor is short-circuited to ground when
powered on, if this fault occurs, the fault code Err20.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-17
Undervoltage fault automatic reset
selection
0.0%
~
50.0%
10.0%
☆
0: Manual reset, after an undervoltage fault occurs, even if the current bus voltage returns to
normal, the fault still exists, and the undervoltage fault Err12 needs to be cleared manually
1: Automatic reset, after an undervoltage fault occurs, the inverter will follow the current bus
voltage to clear the undervoltage fault Err12 by itself.
C
h
a
p
te
r
6
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...