Chapter 5 Function & Parameter Table
Icons
Content
☆
Indicates that the inverter parameters can be modified during stop and
running (0)
★
Indicates that the inverter is in a running state and cannot be modified (1)
○
Indicates that this parameter is a manufacturer's parameter and cannot
be changed by the user (3)
●
Indicates the actual detection value of the inverter or the manufacturer's
fixed value, which cannot be changed (2)
The function code symbols are explained as follows:
-80-
C
h
a
p
te
r
5
The communication address in the function parameter table is written in hexade
-
cimal.
Enhanced function codes:
Group A0~Group A3, Group B0~Group B6, opened
by function parameter P7-75.
Function
code
Name
Description
(setting range)
Factory
Default
Change
Group P0: Basic function group
P0-00
Product number
Product model: 5 digits display, 2
decimal places
60#.##
●
P0-01
Inverter GP type
display
0: G type
1: P type
0
★
P0-02
Rated current
0.1A
~
3000.0A
Model is
determined
●
P0-03
Motor control
method
Ones place: motor control mode selection
1: Open loop vector control (speed
sensorless vector)
2: VF Control
3: Closed loop vector (with speed sensor
vector)
Tens place: motor type selection
0: Asynchronous motor
1: Synchronous motor
2
★
P0-04
Run command
source
0: Operation panel running command
channel (LED off)
1: Terminal command channel (LED on)
2: Communication command channel
(LED flashes)
0
★
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...