Chapter 6 Description of Function Codes
-222-
Figure 6-30. Multi-point curve corresponding diagram
Function
code
Name
Description
(setting range)
Factory
Default
Change
PE-24
AI1 set jump point
-100.0%
~
100.0%
0.0%
☆
PE-25
AI1 sets the jump range
0.0%
~
100.0%
0.5%
☆
The analog input AI1
~
AI2 of KD600 all have the function of setting value jumping.
The jump function means that when the corresponding setting of the analog quantity chang-
es between the upper and lower intervals of the jump point, the corresponding setting value
of the analog quantity is fixed to the value of the jump point.
For example: the voltage of the analog input AI1 fluctuates around 5.00V, the fluctuation ran-
ge is 4.90V~5.10V, the minimum input of AI1 is 0.00V corresponds to 0.0%, and the maxim-
um input of 10.00V corresponds to 100.%, then the detected AI1 corresponds to the setting It
fluctuates between 49.0% and 51.0%. Set AI1 to set jump point PE-24 to 50.0%, set AI1 to
set jump amplitude PE-25 to 1.0%, then when the above AI1 input is processed by the jump
function, the corresponding setting of AI1 input is fixed to 50.0%. AI1 is transformed into a
stable input, eliminating fluctuations.
Group PF: Manufacturer parameters
Manufacturer's parameter group, which cannot be changed by the user.
C
h
a
p
te
r
6
AI corresponding setting
Corresponding setting
of AI max. input
Corresponding setting
of Max.input of AI
0 V (0 mA)
Corresponding setting of
Corresponding setting
of AI min. input
AI curve
AI curve
AI input
voltage
10 V (20 mA)
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...