
-129-
Chapter 6 Description of Function Codes
When the auxiliary frequency source is used as an independent frequency reference chann-
el, its usage is the same as that of the main frequency source X.
When the auxiliary frequency source is used as the superposition reference (the one digit of
P0-10 is 1, 2, 3, 4), it has the following special features:
1. When the auxiliary frequency source is a digital reference, the preset frequency (P0-11)
does not work. It can be performed on the basis of the main reference frequency through the
increase and decrease keys of the keyboard (or UP and DOWN of the multi-function input
terminal). Adjust up and down.
2. When the auxiliary frequency source is given by analog input (AI1, Ai2), 100% of the input
setting corresponds to the range of auxiliary frequency source (see the description of P0-08
and P0-09). If you need to adjust up and down on the basis of the main given frequency, ple-
ase set the corresponding setting range of the analog input to -n% to +n% (refer to the
description of P5-15 to P5-24).
Tip: The auxiliary frequency source Y selection cannot be the same as the main frequency
source X setting value, that is, the main and auxiliary frequency sources cannot use the
same frequency given channel.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P0-07
Auxiliary frequency
source Y selection
0~8
0
★
0: relative to the maximum frequency;
1: relative to frequency source X;
P0-08 is used to determine the relative object of this range. If it is relative to the maximum
frequency (P0-14), its range is a fixed value. If it is relative to the main frequency source X,
its range will change with the main frequency X. and change.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P0-08
Auxiliary frequency
source Y range selection
0~1
0
☆
When the frequency source is selected as frequency superposition given (refer to P0-10 sett
-
ing), it is used to determine the adjustment range of the auxiliary frequency source.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P0-09
Auxiliary frequency
source Y range
0% to 100%
100%
☆
C
h
a
p
te
r
6
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...