-166-
Chapter 6 Description of Function Codes
Function
code
Name
Description
(setting range)
Factory
Default
Change
P5-41
AI1 is selected as DI terminal
function
0
~
53
0
★
P5-42
Function selection selection when
AI2 is used as DI terminal
0
~
53
0
★
This parameter sets whether to use AI as a digital DI terminal. When AI is used as a digital
DI terminal, its function is exactly the same as that of ordinary DI.
Special attention is: the input range of AI is still unchanged from 0 to 10V. When the AI volta-
ge is >6V, it is a high level, and when it is <4V, it is a low level. There is a 2V hysteresis in
between. That is, when AI rises from 0V to >6V, it is a high level, and it is a low level when it
decreases from >6V to 4V.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P5-44
Valid mode selection when AI is
used as DI terminal
0X00
~
0X11
0X00
☆
This parameter is used to set the level selection when AI is used as a digital DI terminal.
0: Active high level, AI is high level when AI rises from 0V to >6V, and is low level when it de
-
creases from >6V to 4V.
1: Low level is active, AI is low level when AI rises from 0V to <6V, and it is low level when it
decreases from >6V to 4V.
Ones place, AI1:
Ten, AI2:
Function
code
Name
Description
(setting range)
Factory
Default
Change
P5-45
AI curve selection
00
~
22
00
☆
This parameter is used for AI curve selection, 0 is a straight line, 1 and 2 are 4-point curves.
And each curve has corresponding function code settings.
Ones place: AI1
0: 2-point straight line P5-15
~
P5-19
1: Multi-point curve 1: PE-00
~
PE-07
2: Multi-point curve 2: PE-08
~
PE-15
C
h
a
p
te
r
6
Содержание 2S-0.4G-B
Страница 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Страница 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Страница 126: ...Function Parameter Table Chapter 6...
Страница 245: ......
Страница 249: ......
Страница 255: ......
Страница 287: ...216 286 3 Wiring diagram Single Phase 220V Three Phase 380V U V W Ground Wire Chapter 10 Chapter 10 Appendix...
Страница 300: ...Version 1 0 Design date August 26 2022...