96 - 23/May/97
Auxiliary HV referred voltages not norm.
Indicated by: LED DRVF, optoisolated output DRIVE OK, bit N of the FA string (see FA
command).
Set condition: when the level of auxiliary voltages referred to power stage (-HV) becomes out
of tolerance.
Effect: inhibit torque of all axes of the module.
Reset condition: if the condition is not present anymore at analog level (with hysteresis) reset
button on drive or send pulse to REM RESET.
Drive overtemperature.
Indicated by: LEDs DRVF and DRV OVT, optoisolated output DRIVE OK, bit O of the FA
string (see FA command).
Set condition: when a limit temperature is reached on the heatsink.
Effect: inhibit torque of all axes of the module.
Reset condition: if the condition is not present anymore power off and on monophase
voltage.
Notes: the temperature limit is detected by thermo-switch.
IT
Indicated by: LED DRVF, bit G of the FA string (see FA command).
Set condition: when the integral value IT ( integral of current in the motor multiplied by the
time ) is over taken.
Effect: when the fault is going on the current limit is reduced to the level of the motor rated
current (set by PC command).
Reset condition: if the condition is not present anymore, the protection is reset. Push button
on drive or send pulse to REM RESET to reset the fault status in FA string.