91 - 23/May/97
3.2.49 Command: VS - VELOCITY STRUCTURE
Function:
it allows to set 4 different structures of the velocity control. All the
structures have a digital low pass filter processing the speed
reference or the speed error signal. The cutoff frequency of this
filter can be adjusted by DF parameter (see DF). The value DF=0
switches the filter OFF.
VS=0 selects the speed controller having the feedback KP and KI
gains four times higher than the standard gains and a digital low
pass filter processing the speed reference signal.
This structure should be used in applications where the analog
speed reference lines from the CNC are noisy, and high gains are
required.
VS=1 selects the speed controller having standard feedback KP
and KI gains and a digital low pass filter processing the speed
reference signal.
This structure should be used in applications where the analog
speed reference lines from the CNC are noisy, and normal gains
are required.
VS=2 selects the speed controller having the feedback KP and KI
gains four times higher than the standard gains and a digital low
pass filter processing the speed error signal.
This structure should be used in applications with high ratios
between load and motor inertia (inertia mismatch), and high gains
are required.
VS=3 selects the speed controller having standard feedback KP
and KI gains and a digital low pass filter processing the speed
error signal.
This structure should be used in applications with high ratios
between load and motor inertia (inertia mismatch), and normal
gains are required.
Syntax:
data monitoring:
n
address VS <CR>
data input:
n
address VS n <CR>
Address type:
axis
Unit of measure:
-
Range:
0 to 3.
VS=0: gains multiplied by 4, reference filtering
VS=1: standard gains, reference filtering
VS=2: gains multiplied by 4,error filtering
VS=3: standard gains , error filtering
Default:
1
Password:
yes
(
∗
) addressing:
no
Opposite to:
-
See also:
DF
Note: the VS command must be executed with digital Drive Enable disabled (via OF command) and the opto
Drive Enable enabled.
REMARK: to change DBM 01 with DBM 03 with same gains it is necessary to:
1. If PR=1 (motor poles=resolver poles) set VS=1 or VS=3
2. If PR
≠
1 (ex. FAS T motor with 2 pole resolver) set VS=0 or VS=2