125 - 23/May/97
6.2.4 FILTER INSTALLATION
- The filter must be mounted on the same panel as the drive.
CAUTION: leave a clear space of at least 60mm around the filter for air circulation.
- The filter must be connected as close as possible to the drive input. If the separation
between filter and drive exceeds around 30 cm (1 ft.) then a flat cable should be used for
the RF connection between filter and drive
REMARK: when mounting the drive and the filter to the panel, it is essential that any paint or
other covering material be removed before mounting the drive and the filter.
- The maximum torque of mounting screws
is as follows:
FILTER
Max
torque
FN 250 - 6/07
0.8 Nm
FN 258 - 7/07
0.8 Nm
FN 258 - 16/07
0.8 Nm
FN 258 - 30/07
1.8 Nm
FN 258 - 42/07
1.8 Nm
FN 258 - 55/07
3.0 Nm
FN 258 - 75/34
3.0 Nm
FN 258 - 100/35
4.0 Nm
- The filter can produce high leakage
currents (see Table)
FILTER
Max leakage current
FN 250 - 6/07
1.3 mA
FN 258 - 7/07
17 mA
FN 258 - 16/07
19 mA
FN 258 - 30/07
25 mA
FN 258 - 42/07
26 mA
FN 258 - 55/07
26 mA
FN 258 - 75/34
26 mA
FN 258 - 100/35
26 mA
- The capacitors within the filters have
discharge resistors.
CAUTION: the filter must be connected
to ground before connecting the supply
WARNING: HIGH VOLTAGE -
DISCHARGE TIME APPROX. 10
seconds
- Where single phase power supply is
needed, the single phase filter can be
installed on the fan housing.
Figure 6.1 shows installation and wiring
of FN 250 6/07 filter on fan housing of
DBM 03 drive.
FIG. 6.1 - FN 250-6/07 FILTER
INSTALLATION ON DBM 03 DRIVE
To
Fans
230V G
N
D