Right Lead Current Value
Current reading of the right sensor probe. May be a temperature or humidity reading, depending on the connected
sensor.
Right Lead Offset
Correction (calibration) value added to the reading. Used in the event that the sensor reading is incorrect.
•
May be a positive or negative value.
9.5 Supply Sensors
When the supply air sensor is set as the control sensor for temperature, additional supply air configuration parameters
(valve pulse, cooling filters and return compensation) can be used to enhance the supply air control.
The valve pulse and cooling filter timer can be adjusted to prevent oscillation around the supply setpoint and still allow for
rapid cooling-capacity adjustments to compensate for heat load changes. Contact Vertiv™ technical support for
adjustments.
NOTE: Supply control air temperature sensors are required to use Optimized Aisle Teamwork (mode 3).
NOTE: On units equipped with a 3P actuator type valve, response can be improved by using the feedback signal.
Vertiv™ | Liebert® iCOM™ Installer/User Guide
88
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...