8.1.1 Configuring BMS Communication with IntelliSlot Card
Modbus, BACnet, SNMP, SMS and HTTP communication cannot be configured via iCOM. To set up third-party protocols,
refer to the appropriate Liebert® IntelliSlot Card user manual available at https://www.vertiv.com/en-us/support/.
NOTICE
Risk of loss of communication with Liebert® IntelliSlot cards. Can cause operational problems.
Do not change the monitoring address of the IntelliSlot card (set at 3) unless directed by a technical support
representative.
To Set Up Communication with a Card
1.
Touch
, then
>
BMS & Teamwork
>
BMS Setup
. The BMS SETUP panel opens.
2.
Select
IntelliSlot Card Settings
and refer to
below, to make selections.
3.
Touch
Save
.
NOTE: Depending on the type of thermal management unit, included components, and control settings of your
system, all of the options listed may not be available on your iCOM display.
IntelliSlot Options
Monitoring Address
Address used by an optional, installed IntelliSlot card. The factor default is 3.
•
Do not modify the monitoring address unless directed to do so by Vertiv™ technical support.
Monitoring Protocol
Protocol used for communication with BMS. Options are:
•
Velocity V3: Legacy Velocity communication card
•
IGM: IGMNet communication cards
•
Velocity V4: Liebert IS-UNITY card.
•
Embedded: Embedded IS-UNITY function
•
Embedded & IS V4 Both Embedded Unity function and Velocity V4 for an optionally installed IS-UNITY card
8.1.2 Setting BMS Control Settings
1.
Touch
, then
>
BMS & Teamwork
>
BMS Setup
> C
ontrol Settings
. The CONTROL SETTINGS
secondary panel opens.
2.
Adjust the settings, and touch
Save
. The settings are configured.
NOTE: Use Configure Timeout to configure the setpoints used in the event of an outage and BMS takes control. See
Vertiv™ | Liebert® iCOM™ Installer/User Guide
80
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...