Line
ID
Parameter
Name
Range
Default
Setting
Description
U219
Remote
Sensor
Alarms
0 =
Disabled
1 = Com
Set
2 = Sep
Set
Disabled
Enables or disables the remote sensor alarms. When enabled, the remote temperature values will be
compared to a high and low setting.
U220
High Remote
Temperature
34 -
210°F
1.0 -
99.0 °C
90 °F
Enables or disables remote sensor temperature alarms. When enabled, the high and low remote
temperature alarm will allow a user to adjust the point at which the actual remote temperature activates a
High/Low temperature alarm. This parameter is used when common alarm points will be shared by all
sensors. Otherwise, the remote sensors can be set individually.
Low Remote
Temperature
34 -
210°F
1.0 -
99.0 °C
55 °F
U224-
U233
High Remote
01-10
34 -
210°F
1.0 -
99.0 °C
90 °F
Sets the high and low remote temperature sensor alarm points individually for each sensor when the
parameter separate thresholds is set to disabled
Low Remote
01-10
34 -
210°F
1.0 -
99.0 °C
55 °F
U235
Static
Pressure
Messages
Disabled
Enabled
Disabled
Enables or disables static pressure messages.
U236
High Static
Pressure
(inWC)
0.010 -
1.405
inWC
1.284
inWC
Sets the pressure at which the High Static Pressure Alarm is activated (inWC, Pa)
High Static
Pressure
(Pa)
2 - 350
Pa
320 Pa
U237
Low Static
Pressure
(inWC)
0.000 -
1.395
nWC
0.000
inWC
Sets the pressure at which the Low Static Pressure Alarm is activated (inWC, Pa)
Low Static
Pressure
(Pa)
0 - 348
Pa
0 Pa
U238
SP Messages
During Unit
Off
No
Yes
No
Enables or disables Static Pressure messages when the unit is OFF
U239
SP Messages
on Fan
Adjust
No
Yes
No
Enables or disables the static pressure messages when the fan as been adjusted due to special events.
These events include an adjustment for heating, humidification, dehumidification, motor overload / EC fan
fault or loss of airflow.
Table B.3 User Menu Alarm Settings by Line ID (continued)
147
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...